Multi Splits Series HK
Product specification 8 General Information Model Indoor Unit AWSI-HND009-N11 AWSI-HND012-N11 Installation Method of Pipe Flared Flared Charact
Electrical Control Function 98 Electrical Control System 38 EXV open angle for B indoor unit If the value is higher than 99, the digital display tu
Electrical Control Function Electrical Control System 99 T1 Ts40a31-13120bcdef2 Capacity area a b c d e f Norm value (N) 3 2 1.5 1 0.5 0 1.3.12.4
Troubleshooting 100 Electrical Control System 2. Troubleshooting 2.1 Display board 2.1.1 Icon explanation on indoor display board (HKD& HND).
Troubleshooting Electrical Control System 101 2.1.3 Icon explanation on indoor display board (Compact cassette). 2.1.4 Icon explanat
Troubleshooting 102 Electrical Control System 2.2 Indoor unit malfunction For HKD,HND Display Operation lamp flash times Timer lamp F
Troubleshooting Electrical Control System 103 For Console: NO. Malfunction Running lamp Timer lamp Defrosting lamp 1 Open or short circuit of T1 te
Troubleshooting 104 Electrical Control System 2.3 Outdoor unit malfunction Display LED STATUS E0 Outdoor EEPROM malfunction E2 Indoor / outdoor uni
Troubleshooting Electrical Control System 105 2.4 Solving steps for typical malfunction 2.4.1 For the indoor unit 2.4.1.1 Indoor EEPROM malfunction
Troubleshooting 106 Electrical Control System 2.4.1.2 Indoor / outdoor units communication error Indoor / outdoor units communication errorStart
Troubleshooting Electrical Control System 107 Pic 2: :IPM (For dual/tri-zone) Self-Check Power, Operating Self-Check
Product specification General Information 9 Model Indoor Unit AWSI-HKD012-N11 AWSI-HKD018-N11 Installation Method of Pipe Flared Flared Characteri
Troubleshooting 108 Electrical Control System . PIC3 :Main board LED when power on and unit standby. PIC 4: check point button, Press 1 t
Troubleshooting Electrical Control System 109 2.4.1.3 indoor unit fan speed has been out of control Shut off the power supply and turn it on 1 mi
Troubleshooting 110 Electrical Control System For console: 546321 NO. Color 1 Red 2 --- 3 White 4 Blue 5 Yellow 6 Black For oth
Troubleshooting Electrical Control System 111 For console: 546321 DC motor voltage input and output For HKD &HND: NO. Color Signal Voltage 1
Troubleshooting 112 Electrical Control System 2.4.1.4 Open or short circuit of temperature sensor. Check the connections between temperature sen
Troubleshooting Electrical Control System 113 2.4.2 For the outdoor unit 2.4.2 1 Outdoor EEPROM malfunction(ODU E0) If the EEPROM chip is welded o
Troubleshooting 114 Electrical Control System 2.4.2.2 Communication malfunction between IPM board and outdoor main board(ODU E3) Communication m
Troubleshooting Electrical Control System 115 2.4.2.3 Voltage protection(ODU E5) Voltage protection Check the voltage of outdoor unit power suppl
Troubleshooting 116 Electrical Control System 2.4.2.4 Outdoor unit fan speed has been out of control (E8) Shut off the power supply and turn it
Troubleshooting Electrical Control System 117 Index 1: 1.Outdoor DC fan motor(control chip is inside fan motor) Measure the resistance value of eac
Product specification 10 General Information Model Indoor Unit AWSI-CBD012-N11 Installation Method of Pipe Flared Characteristics Units Cooli
Troubleshooting 118 Electrical Control System 2.4.2.5 High pressure protection (ODU P1) (For AWAU-YCZ430-H11, AWAU-YCZ536-H11) High pressure pro
Troubleshooting Electrical Control System 119 2.4.2.6 Low pressure protection (ODU P2) (For AWAU-YCZ430-H11, AWAU-YCZ536-H11) Low pressure protect
Troubleshooting 120 Electrical Control System 2.4.2.7 Current protection of compressor(ODU P3) Current protection of compressorJudge 1: Check wh
Troubleshooting Electrical Control System 121 2.4.2.8 Temperature protection of compressor discharge(ODU P4) Temperature protection of compressor d
Troubleshooting 122 Electrical Control System 2.4.2.9 High temperature protection of condenser(ODU P5) When outdoor pipe temperature is more tha
Troubleshooting Electrical Control System 123 2.4.2.10 IPM module protection(ODU P6) IPM module protectionCheck whether the voltage range of P-
Troubleshooting 124 Electrical Control System 2.4.3 Main parts check Spec. Indoor unit Model AWSI-HND009-N11 AWSI-HND012-N11 AWSI-HND018-N11 Ind
Troubleshooting Electrical Control System 125 1. Temperature sensor checking Disconnect the temperature sensor from PCB, measure the resistance v
Troubleshooting 126 Electrical Control System Appendix 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4,T2B (℃--K) ℃ K Ohm ℃ K Ohm ℃
Troubleshooting Electrical Control System 127 Appendix 2 Temperature Sensor Resistance Value Table for T5 (℃--K) ℃ K Ohm ℃ K Ohm ℃ K Ohm ℃ K Ohm -
Indoor Units Indoor Units 11 Part 2 Indoor Units HKD Type ... 12 HND Typ
Troubleshooting 128 Electrical Control System 2.Compressor checking Measure the resistance value of each winding by using the tester. Positi
Troubleshooting Electrical Control System 129 3. IPM continuity check Turn off the power, let the large capacity electrolytic capacitors discharge
SERVICE MANUAL Multi Splits Series
HKD Type 12 Indoor Units HKD Type 1. Function ... 13 2. Dimensions .
Function Indoor Units 13 1. Function Killer Of FormaldehydeSilver Ico Filter(O)Vitamin C Filter(O)3M HAM Filter(O)Bio Filter(O)Golden Fin(O)Ionizer
Dimensions 14 Indoor Units 2. Dimensions WDH Model L(mm) R(mm) H(mm) Dimension of installation hole(mm) AWSI-HKD009-N11 100 95 45 ¢65 A
Wiring Diagrams Indoor Units 15 3. Wiring Diagrams AWSI-HKD009-N11, AWSI-HKD012-N11, AWSI-HKD018-N11
Exploded View and Spare Part list 16 Indoor Units 4. Exploded View and Spare Part list Exploded View of indoor unit: AWSI-HKD009-N11
Exploded View and Spare Part list Indoor Units 17 Spare part list of indoor unit: AWSI-HKD009-N11 No. Part Name Qty BOM Code No. Part Name
Contents Contents i Part 1 General Information ...
Exploded View and Spare Part list 18 Indoor Units Exploded View of indoor unit: AWSI-HKD012-N11
Exploded View and Spare Part list Indoor Units 19 Spare part list of indoor unit: AWSI-HKD012-N11 No. Part Name Qty BOM Code No. Pa
Exploded View and Spare Part list 20 Indoor Units Exploded View of indoor unit: AWSI-HKD018-N11
Exploded View and Spare Part list Indoor Units 21 Spare part list of indoor unit: AWSI-HKD018-N11 No. Part Name Qty BOM Code No. Part
HND Type 22 Indoor Units HND Type 1. Function ... 23 2. Dimensions ...
Function Indoor Units 23 1. Function Cold catalyst filterPlasma(O)Silver Ico Filter(O)Vitamin C Filter(O)3M HAM Filter(O)Bio Filter(O)Golden Fin(O)
Dimensions 24 Indoor Units 2. Dimensions W D Model W D H AWSI-HND009-N11 750 198 280 AWSI-HND012-N11 835 198 280 AWSI-HND018-N11 990 218 3
Dimensions Indoor Units 25 Model L(mm) R(mm) H(mm) Dimension of installation hole(mm) AWSI-HND009-N11 180 110 45 ¢65 AWSI-HND012-N11 140 110 45
Wiring Diagrams 26 Indoor Units 3. Wiring Diagrams AWSI-HND009-N11, AWSI-HND012-N11 AWSI-HND018-N11
Exploded View and Spare Part list Indoor Units 27 4. Exploded View and Spare Part list Exploded View of indoor unit: AWSI-HND009-N11
General Information General Information 1 Part 1 General Information 1. Model Lists ...
Exploded View and Spare Part list 28 Indoor Units Spare part list of indoor unit: AWSI-HND009-N11 No. Part Name Qty BOM Code No. Part N
Exploded View and Spare Part list Indoor Units 29 Exploded View of indoor unit: AWSI-HND012-N11
Exploded View and Spare Part list 30 Indoor Units Spare part list of indoor unit: AWSI-HND012-N11 No. Part Name Qty BOM Code No.
Exploded View and Spare Part list Indoor Units 31 Exploded View of indoor unit: AWSI-HND018-N11
Exploded View and Spare Part list 32 Indoor Units Spare part list of indoor unit: AWSI-HND018-N11 No. Part Name Qty BOM Code No. P
Light Commercial Indoor Units 33 Light Commercial 1. Features ... 34 2. D
Features 34 Indoor Units 1. Features 1.1 Four-way cassette type(compact) ⑴ New panel 360°surrounding air outlet design, affords comfortab
Features Light Commercial 35 ⑸ Air passage function Reserves the space for air outlet from the side of indoor unit; It’s availed
Features 36 Indoor Units 1.2 A5 Duct ⑴ Installation accessories: (Optional) Front Board, Canvas Air Passage, Filter, Panel, for easy installa
Features Light Commercial 37 Replace the motor or centrifugal fan Remove the ventilated panel firstly. Remove a half of blower housing and take
Model Lists 2 General Information 1. Model Lists 1.1 Indoor Units Cooling & Heating Indoor units type Indoor units model Capacity(Btu/h) Pow
Features 38 Indoor Units ⑺ Built-in display board The standard indoor unit can be controlled by wired controller. There is a display
Features Light Commercial 39 1.3 Console (1) Consumes up to 30% less energy than non-inverter units ——DC inverter compressor ——indoor fan motor ad
Dimensions 40 Indoor Units 2. Dimensions 2.1 Four-way cassette type(compact): 2.2 A5 Duct HGEFABDC LM
Dimensions Light Commercial 41 Model Outline dimension(mm) Air outlet opening size Air return opening size Size of outline dimension mounted plug
Service Space(unit:mm) 42 Indoor Units 3. Service Space(unit:mm) 3.1 Four-way cassette(compact) 3.2 A5 Duct Ensure enough space required fo
Service Space(unit:mm) Light Commercial 43 3.3 Console
Wiring Diagrams 44 Indoor Units 4. Wiring Diagrams AWSI-CBD012-N11 AWSI-DCD012-N11
Wiring Diagrams Light Commercial 45 AWSI-DCD012-N11
Wiring Diagrams 46 Indoor Units AWSI-XAD012-N11
Exploded View and Spare Part list Light Commercial 47 5. Exploded View and Spare Part list Exploded View of indoor unit:AWSI-CBD012-N11
External Appearance General Information 3 2. External Appearance 2.1 Indoor Units HKD HND Four-way cassette(Compact) Duct Console 2.2 Outd
Exploded View and Spare Part list 48 Indoor Units Spare part list of indoor unit:AWSI-CBD012-N11 No. Part Name Qty BOM Code No. Part Na
Exploded View and Spare Part list Light Commercial 49 Exploded View of indoor unit: AWSI-DCD012-N11
Exploded View and Spare Part list 50 Indoor Units Spare part list of indoor unit: AWSI-DCD012-N11 No. Part Name Qty BOM Code No. Part Nam
Exploded View and Spare Part list Light Commercial 51 Exploded View of indoor unit:AWSI-XAD012-N11
Exploded View and Spare Part list 52 Indoor Units Spare part list of indoor unit:AWSI-XAD012-N11 No. Part Name Qty BOM Code No. Part Na
Outdoor Units Outdoor Units 53 Part 3 Outdoor Units 1. Dimensions ... 54 2. Se
Dimensions 54 Outdoor Units 1. Dimensions AWSI-XAD012-N11 560 W1H6D1 335D2 360845 W313D3335D1R6R5A122A250B1120110B2700W273585858110H1H2200.
Dimensions Outdoor Units 55 AWAU-YCZ327-H11 900 W590 W1860H12D2 355D1 333302D3333D1
Dimensions 56 Outdoor Units AWAU-YCZ430-H11 900 W590 W1860H12D2 355D1 333302D3333D1509790B2B18A25555 55 55 55 55 5511062W2H1H2R6238.4285.7L1
Dimensions Outdoor Units 57 AWAU-YCZ536-H11
Product specification 4 General Information 3. Product specification Model Outdoor Unit AWAU-YCZ218-H11 Installation Method of Pipe 2 x AWSI-HND
Service Space 58 Outdoor Units 2. Service Space More than 60cmMore than 30cmMore than 60cmMore than 200cmAir inletAir inletMore than 30cmAir ou
Refrigeration Cycle Diagram Outdoor Units 59 3. Refrigeration Cycle Diagram 3.1 Refr
Refrigeration Cycle Diagram 60 Outdoor Units LIQUID VALVE AGAS VALVE AHEATEXCHANGE(EVAPORATOR)HEATEXCHANGE(CONDENSER)Compressor4-WAY VALVECOOLI
Wiring Diagrams Outdoor Units 61 4. Wiring Diagrams AWAU-YCZ218-H11 AWAU-YCZ327-H11
Wiring Diagrams 62 Outdoor Units AWAU-YCZ430-H11 AWAU-YCZ536-H11
Indoor units combination Outdoor Units 63 5. Indoor units combination 5.1 Indoor uni
Operation Limits 64 Outdoor Units 6. Operation Limits Temperature Mode Cooling operation
Sound Levels Outdoor Units 65 7. Sound Levels H1.0mOutdoor UnitMicrophone Note: H= 0.
Exploded View and Spare Part list 66 Outdoor Units 8. Exploded View and Spare Part list Exploded View of outdoor unit: AWAU-YCZ218-H11
Exploded View and Spare Part list Outdoor Units 67 Spare part list of outdoor unit:
Product specification General Information 5 Model Outdoor Unit AWAU-YCZ327-H11 Installation Method of Pipe 3 x AWSI-HND009-N11 3 x AWSI-HKD009-N11
Exploded View and Spare Part list 68 Outdoor Units Exploded View of outdoor unit: AWAU-YCZ327-H11
Exploded View and Spare Part list Outdoor Units 69 Spare part list of outdoor unit:
Exploded View and Spare Part list 70 Outdoor Units Exploded View of outdoor unit: AWAU-YCZ430-H11
Exploded View and Spare Part list Outdoor Units 71 Spare part list of outdoor uni
Exploded View and Spare Part list 72 Outdoor Units Exploded View of outdoor unit: AWAU-YCZ536-H11
Exploded View and Spare Part list Outdoor Units 73 Spare part list of outdoor unit:
Installation 74 Installation Part 4 Installation 1.Wrench torque sheet for installation ... 75
Wrench torque sheet for installation Installation 75 1. Wrench torque sheet for installation Outside diameter Torque Additional tightening torque
Pipe length and the elevation 76 Installation
Installation for the first time Installation 77 4. Installation for the first time Air and moisture in the refrigerant system have undesirable eff
Product specification 6 General Information Model Outdoor Unit AWAU-YCZ430-H11 Installation Method of Pipe 4 x AWSI-HND009-N11 4 x AWSI-HKD009-
Installation for the first time 78 Installation 7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after th
Installation for the first time Installation 79 7). Mount the valve stems nuts and the service port cap. Be sure to use a torque wrench to tighten
Adding the refrigerant after running the system for many years 80 Installation 5. Adding the refrigerant after running the system for many year
Re-installation while the indoor unit need to be repaired Installation 81 6. Re-installation while the indoor unit need to be repaired 6.1. Collec
Re-installation while the indoor unit need to be repaired 82 Installation 6.2. Air purging by the refrigerant Procedure: 1). Confirm that both
Re-installation while the outdoor unit need to be repaired Installation 83 Be sure to check the gas leakage. 7. Re-installation while the outdoor
Re-installation while the outdoor unit need to be repaired 84 Installation 7.2. Refrigerant charging Procedure: 1). Connect the charge hose to
Electrical Control System Electrical Control System 85 Part 5 Electrical Control System 1. Electrical Control Function ...
Electrical Control Function 86 Electrical Control System 1. Electrical Control Function 1.1 Definition T1: Room Air Thermistor (RAT) T2: Ind
Electrical Control Function Electrical Control System 87 COOL_F6 ICOOLLMT2 COOL_F5 ICOOLLMT1 If the current frequency is lower than COOL_F4, the fr
Product specification General Information 7 Model Outdoor Unit AWAU-YCZ536-H11 Installation Method of Pipe 5 x AWSI-HND009-N11 5 x AWSI-HKD009-N11
Electrical Control Function 88 Electrical Control System 3.53.0HighLow1.0Medium1.5 For HKD,HND, Console abcd5.04.02.51.06.0T1-24eH(H-L)*0.75+L(H-L
Electrical Control Function Electrical Control System 89 T4A DC_FAN_HI_SPD_ADDB DC_FAN_MID_SPD_ADDC DC_FAN_MIN_SPD_ADDD DC_FAN_SLOW_SPD_ADDE DC_FAN
Electrical Control Function 90 Electrical Control System The auto fan acts as below rules: abcd5.04.02.51.06.0T1-TseH(H-L)*0.75+L(H-L)*0.5+L(H-L)*
Electrical Control Function Electrical Control System 91 T4E DC_FAN_SSLOW_SPD_ADDD DC_FAN_SLOW_SPD_ADDC DC_FAN_MIN_SPD_ADDB DC_FAN_MID_SPD_ADDA DC_
Electrical Control Function 92 Electrical Control System -1.0-2.0-3.0-4.00.0T1-Ts+ΔTL(H+-L)*0.4+L(H+-L)*0.6+L-5.0-6.0-6.5H+(H+-L)*0.8+L(H+-L)*0.6+L
Electrical Control Function Electrical Control System 93 ----T3 rises to be higher than TCDE1℃. ----T3 keeps to be higher than TCDE2℃ for 80 secon
Electrical Control Function 94 Electrical Control System Low indoor room temperature protection All protections are active and the same as that in
Electrical Control Function Electrical Control System 95 1.3.10 Forced operation function 1.3.10.1 Enter forced operation function: Press the touch
Electrical Control Function 96 Electrical Control System from follow-me signal every 3 minutes. 3) The PCB will take action to the mode ch
Electrical Control Function Electrical Control System 97 function, it will display No. N with 1.5s, meanwhile the low bit decimal of digit display