Airwell GC 43 Manual do Utilizador Página 51

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 74
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 50
49
XAO Series CX 25 X 1100 AO X 1900 AO X 2450 AO X 3250 AO X 4650 AO
Cooling capacity kW 8.30 11.6 18.5 23.6 32 45.7
Power Input kW 2.55 3.8 5.5 7.115 9.75 13.9
EER kW 3.26 3.05 3.36 3.31 3.28 3.29
Cooling circuit 111112
Compressor type Piston Piston Piston Piston Piston Piston
Noise level (Pressure NS) dB(A) 50 52 55 58 64 60
Air distribution plenum: height mm 300 220 260 350 350 400
Weight kg 125 151 199 305 380 565
Dimensions (WxDxH) mm
800x407x1280 890x430x1540 1000x500x1735 1300x600x1840 1530x600x1840 1715x790x1970
Aeraulic characteristics
- Nominal air flow m
3
/h 1500 2000 3200 4500 5800 9000
- Air flow range (min/max) m
3
/h 1160/1750 1500/2500 2500/3800 3600/5400 4600/7000 7200/10800
- Available static pressure (min/max) daPa 0/8 0/20 0/30 0/20 0/25 0/23
Hydraulic characteristics
- Waste water Flow m
3
/h 0.37 0.58 0.92 1.45 2 2.8
Pressure drop kPa 25 22 18 42 40 18
- Recycled water Flow m
3
/h 1.36 2.1 3.4 4.3 5.8 8.3
Pressure drop kPa 180 50 70 60 40 56
1~230V With pressostatic water valve 7XU012001 -----
3N~400V With pressostatic water valve ---7XU0120167XU0120237XU012024
3N~400V Without pressostatic water valve 7XU012002 7XU012004 7XU012008 7XU012013 7XU012015 7XU012017
Linking specifications between indoor and outdoor units
Power supply 1~230V
Power cable section mm
2
3x2.5 -----
Fuse rating am A 16 -----
Power supply 3N~400V
Power cable section mm
2
5x1.5 5x1.5 5x1.5 5x1.5 5x1.5 5x1.5
Fuse rating am A 3x10 3x12 3x20 3x25 3x32 3x50